Each entry is quoted from its source and linked to it. The full set is in the standards reference.
Floating or glued down
Yes. The EPLF, the association of European laminate flooring producers, states in its technical bulletin on installation that laminate floor coverings are by conception intended for floating installation, and that a full-surface adhesive bond is an exception used only under special circumstances, for example at the specific request of the client. Before bonding a laminate floor over its full surface, installers are urged to contact the manufacturer or supplier to establish whether the product is suitable or approved for that type of installation.
| laminate floor coverings – method by design | floating installation |
|---|
| full-surface adhesive bond | exception, only under special circumstances and after checking suitability/approval with the manufacturer |
|---|
“Under special circumstances, for example at the specific request of the client, it may be necessary to install laminate floor coverings using a full-surface adhesive bond, despite the fact that by conception laminate floor coverings are intended for floating installation.”
Source: EPLF Technical Bulletin – Installation of Laminate Floor Coverings (English edition 06/2022), European Producers of Laminate FlooringThe expansion gap
The EPLF, the European association of laminate flooring producers, recommends an edge gap of 8 mm to 12 mm on all sides of a floating floor, so that the covering can expand and contract without lifting.
| recommended edge gap on all sides | 8 to 12 mm |
|---|
“To accommodate such changes, a edge spacing should be observed on all sides. A free space of 8 mm to 12 mm is recommended.”
Source: EPLF Technical Bulletin — Installation of Laminate Floor Coverings (06/2022), 6.4 Edge gapsEN 16354 — how an underlay’s impact sound value is declared
EN 16354 specifies the test methods for the technical characteristics of underlays under laminate floor coverings, impact sound among them, and sets requirements for marking. Neither the standard nor the trade associations publish a typical impact sound figure: the EPLF's technical bulletin says an underlay's ISLam value should be at least 14 dB, tested with the reference floor covering described in EN 16354, and any higher figure on a data sheet is a product-specific declaration by that manufacturer.
| Minimum ISLam impact sound value recommended by the EPLF for an underlay under laminate | 14 dB |
|---|
“The test methods are described in EN 16354 'Laminate floor coverings - Underlays - Specifications, requirements and test methods'. The ISLam value of an underlayment for footstep soundproofing should be at least 14 dB. To express the ISLAM value the reference floor covering described in EN16354:2018 (clause 3.5) has to be used for tests.”
Source: EPLF Technical Bulletin - Underlay Materials under Laminate Floor Coverings - Test Standards and Performance Indicators (English edition 12/2022) · second sourceWhat an underlay is actually for
The MMFA groups the benefits of an underlay under floating multilayer modular flooring into three headings: ensuring a satisfactory installation by levelling unevenness, permanently protecting the floor against wear and against rising residual building moisture, and improving the floor's properties in terms of impact sound, walking noise, heat insulation and walking comfort.
“The requirements for suitable underlays are aimed at protecting the floor from daily wear and tear such as falling objects and walking, as well as shielding the floor from rising residual building moisture or damp.”
Source: Underlays — MMFA (Multilayer Modular Flooring Association)Room conditions at the time of fitting
The MMFA, the European association for multilayer modular floor coverings, requires the flooring to acclimatise for at least 48 hours in the same conditions as the installation area, stored flat and cross-stacked in unopened boxes at roughly 15-25 degrees Celsius and 35 to 65 per cent relative humidity.
| acclimatisation before installation | at least 48 h |
|---|
| storage and acclimatisation temperature | 15-25 °C |
|---|
| storage and acclimatisation relative humidity | 35-65 % |
|---|
“Leave the floor covering to acclimatise in the same environmental conditions as the installation area for a period of at least 48 hours prior to installation. Always store the boards flat and cross-stacked, in their original unopened boxes and at approx. 15-25 °C and between 35 % and maximum 65 % relative humidity.”
Source: Prior to installation — MMFA (Multilayer Modular Flooring Association)BS 8203 — relative humidity limit for a subfloor
UK practice following BS 8203 treats a subfloor as dry enough for resilient floor coverings when hygrometer readings do not exceed 75% relative humidity (65% RH for solid timber coverings), measured with a hygrometer sealed to the surface so that it reaches equilibrium with the base.
| RH limit, resilient floor coverings | 75 % RH |
|---|
| RH limit, solid timber floor coverings | 65 % RH |
|---|
“The base can be considered dry enough to install most floorcoverings if a series of tests produce readings not exceeding 75% R.H. (65% R.H. for solid timber floorcoverings).”
Source: F. Ball and Co. Ltd - Digital Hygrometer, Technical Data SheetThe hygrometer method for subfloor moisture
In UK practice a hygrometer is sealed to the subfloor inside an insulated box with butyl tape and left until the air under the box reaches equilibrium; at least 4 hours before the first reading on a 50 mm screed with the DPM under the screed, and 72 hours where the DPM lies below the base slab.
| minimum time before first reading, 50 mm screed with DPM between base and screed | 4 hours |
|---|
| minimum time before first reading, DPM below the base slab | 72 hours |
|---|
“For 50mm thick screeds, where the damp proof membrane is placed between the base and the screed, a period of at least 4 hours should be allowed before the first reading is taken. For thicker constructions i.e. where the damp proof membrane is placed below the base slab, a period of 72 hours should be allowed to elapse before the first reading.”
Source: Digital Hygrometer - Technical Data Sheet, F. Ball and Co. LtdBS 8204 — surface regularity classes SR1 to SR3
BS 8204 defines three surface regularity classes for screeds and concrete bases, SR1, SR2 and SR3, measured as the maximum deviation below a 2 m straightedge placed directly on the surface.
| SR1 (max deviation under 2 m straightedge) | 3 mm |
|---|
| SR2 (max deviation under 2 m straightedge) | 5 mm |
|---|
| SR3 (max deviation under 2 m straightedge) | 10 mm |
|---|
| straightedge length | 2 m |
|---|
“Surface regularity classes are given in BS 8204 as SR1, SR2 and SR3 relating to 3mm, 5mm and 10mm respectively.”
Source: Surface regularity - straightedge method | The Concrete SocietyHow long a screed takes to dry
BS 8204-1 gives a drying allowance of one day per millimetre of thickness for the first 50 mm of a levelling screed, with longer per-millimetre times above that thickness, so a 50 mm screed drying in good conditions takes roughly two months.
| drying allowance, first 50 mm | 1 day per mm |
|---|
| thickness covered by the 1 day/mm rule | 50 mm |
|---|
| resulting drying time for a 50 mm screed, good conditions | about 2 months |
|---|
“with levelling screeds, one day should be allowed for each millimetre of thickness for the first 50 mm, followed by an increasing time for each millimetre above this thickness. It is therefore reasonable to expect a levelling screed 50 mm thick, drying under good conditions, to be sufficiently dry in about 2 months.”
Source: Drying of Screeds - RonacreteDamp-proof membrane — Approved Document C
Approved Document C, paragraph 4.2, states that floors next to the ground should resist the passage of ground moisture to the upper surface, not be damaged by moisture from the ground or by groundwater, and resist the passage of ground gases.
| paragraph in Approved Document C | 4.2 |
|---|
| requirement covered | C2 Resistance to moisture |
|---|
“Floors next to the ground should: a. resist the passage of ground moisture to the upper surface of the floor; b. not be damaged by moisture from the ground; c. not be damaged by groundwater; d. resist the passage of ground gases.”
Source: Approved Document C - Site preparation and resistance to contaminants and moisture, 2013 edition (HM Government)Cutting waste — how much extra to order
There is no published industry standard for cutting waste; the figures come from manufacturers' own guidance and they vary. Havwoods advises 8-12 % wastage for planks and 15-20 % for patterned floors such as herringbone or chevron. Quick-Step's UK guidance for laminate is 5 % extra in a regular room and 10 % in a room with many angles or curves.
| Wastage allowance, plank floors (Havwoods UK) | 8-12 % |
|---|
| Wastage allowance, herringbone or chevron (Havwoods UK) | 15-20 % |
|---|
| Extra to order, regular room, laminate (Quick-Step UK) | 5 % |
|---|
| Extra to order, room with many angles or curves, laminate (Quick-Step UK) | 10 % |
|---|
“For planks we typically advise on 8-12% wastage and patterned floors, such as herringbone or chevron, may need 15-20% wastage.”
Source: Havwoods UK - FAQs: How Much Wastage Shall I Encounter For? · second sourceBS EN 13329 — laminate floor coverings
BS EN 13329 specifies the characteristics, requirements and test methods for laminate floor coverings with a surface layer based on aminoplastic thermosetting resins, including requirements for marking and packaging. It also contains a classification system based on EN ISO 10874 for areas and levels of use, and it does not cover areas subject to frequent wetting such as bathrooms, laundry rooms or saunas.
“BS EN 13329 specifies characteristics, requirements, and test methods for laminate floor coverings with a surface layer based on amino plastic thermosetting resins. BS EN 13329 specifies requirements for marking and packaging.”
Source: BS EN 13329:2016+A2:2021 | 31 Oct 2021 | BSI Knowledge